KN family of boilers: KN-30
Innovation sized to meet the low fuel use,
low installed cost, small footprint
demands of today's condensing commercial boiler market.
The KN-Series boiler from HydroTherm is the first commercial boiler
to realize condensing efficiencies using a
cast iron heat exchanger. The result is a boiler family that
combines the condition-tolerant and heat-retaining
characteristics of cast iron with the fuel savings of
full modulation condensing performance.
- Low Installation Costs
-
Factory piped & wired packaged boiler in a compact footpring; capable of being rigged via pallet jack through a standard doorway.
-
Single field adjustment required: zero governor gas valve controls CO2 by a simple metric allen key setting.
-
Variable water flow heat exchanger accepts up to 10:1 range, minimizing piping costs
-
Venting runs of up to 120 equivalent feet each, exhaust and air intake.
- Low Operation Costs
-
Unrivaled heat retention: high mass cast iron heat exchanger with 5x the wall thickness of copper holds heat energy longer.
-
State of the art HeatNet integral control provides user-friendly multi-function monitoring of all boiler operations with intuitive diagnostics and easy to read text displays.
-
Down-fire design offers easy accessibility to all components for annual service and maintenance.
- Low Fuel Usage/Emissions
-
92.7% thermal efficiency at full input.
99% combustion efficiency at minimum input (5:1 turndown).
-
Optimal fuel utilization and boiler performance through integral HeatNet control module.
-
Low NOx and CO2 emissions - reduces greenhouse gases - environmentally friendly.
-
Meets South Coast Air Quality Management Division (SCAQMD) rule 1146.2 standards.
- High Performance Engineering
-
Ultra efficient Tru-Flow symmetric air/fuel coupling design burns clean while insuring proper combustion at all firing rates.
-
5:1 continuous modulation for maximum efficiencies at all levels of heat demand.
-
Proven 8,000 btu pilot or "mini burner" with interrupted spark ignition and air-cooled UV sensor for enhanced reliability.
-
Low pressure drop through the boiler does not require high velocities and allows good flow-balancing through multiple boiler configurations with reverse-return piping.
| 3,000,000 BTUH |
|
Nominal |
Min |
Max |
Gas pressure, inches W.C. |
2 |
9 |
14 |
Voltage 240v
3ph 60hz |
|
|
|
| Flow, GPM |
|
45 |
450 |
| Temperature rise, F |
|
20 |
100 |
| Flue length, equiv. Ft. |
|
6 |
120 |
| Air inlet length, equiv. Ft. |
|
0 |
120 |
| Water volume, gals |
28 |
| Flue diameter, in |
8" |
| Current, amps |
6.5 |
| Cv, GPM @ 1psid |
278 |
| Boiler HP |
79 |
| Input MBH |
3000 |
| Output MBH |
2781 |
| Fuel Type |
Nat. Gas/LP |
| ASME Design Data Max |
100PSI +250°F |
| Negative Flue Pressure |
-0.2" W.C. |
| Positive Flue Pressure |
0.9" W.C. |
| Height |
71 13/16" |
| Length |
80 31/32" |
| Width |
31 9/32" |
| LBS. |
3500 lbs |
Improve your boiler efficiency while cutting your outside air louver size by 70 to 80% while maintaining an ideal boiler room environment
INTUITIVE and INTELLIGENT
The HeatNet integrated boiler control built into every KN can connect up to 16 units using only a
standard Ethernet cable: truly plug and play, with no external wall-mounted controls.
View>>
Rep Locator
Use our interactive map of North America to find the sales rep servicing your area.
Find>>