KN family of boilers: KN-6
Innovation sized to meet the low fuel use,
low installed cost, small footprint
demands of today's condensing commercial boiler market.
The KN-Series boiler from HydroTherm is the first commercial boiler
to realize condensing efficiencies using a
cast iron heat exchanger. The result is a boiler family that
combines the condition-tolerant and heat-retaining
characteristics of cast iron with the fuel savings of
full modulation condensing performance.
Click on the links below to learn more
Low Installation Cost
-
Factory piped & wired packaged boiler in a compact footprint; capable of being rigged via pallet jack through a standard doorway.
-
Single field adjustment required: zero governor gas valve controls CO2 by a simple metric allen key setting.
-
Variable water flow heat exchanger accepts up to 10:1 range, minimizing piping costs.
-
Venting runs of up to 80 equivalent feet each, exhaust and air intake.
Low Operation Costs
-
Unrivaled heat retention: high mass cast iron heat exchanger with 5x the the wall thickness or copper holds heat energy longer.
-
State of the art HeatNet integral control provides user-friendly Multi-function monitoring of all boiler operations with intuitive diagnostics and easy to read text displays.
-
Down-fire design offers easy accessibility to all components for annual service and maintenance.
Low Fuel Usage/Emissions
-
88% combustion efficiency a full input. 99% combustion efficiency at minimum input (5:1 turndown).
-
Optimal fuel utilization and boiler performance thru integral HeatNet control module.
-
Low NOx and CO2 emissions - Reduces greenhouse gases.
-
Meets South Coast Air Quality Management Division (SCAQMD) Rule 1146.2 standards.
High Performance Engineering
-
Made in the USA
-
Ultra efficient Tru-Flow symmetric air/fuel coupling design burns clean while insuring proper combustion at all firing rates.
-
5:1 continuous modulation for maximum efficiencies at all levels of heat demand.
-
Proven 8,000 btu pilot or "mini burner" with interrupted spark ignition and air-cooled UV sensor for enhanced reliability.
-
Low pressure drop thru the boiler does not require high velocities and allows good flow-balancing thru multiple boiler configurations with reverse-return piping.
| 600,000 BTUH |
| Nominal | Min | Max |
Gas pressure, inches W.C. | 7 | 2 | 14 |
Voltage, 120 V 1ph 60hz | 120 | 102 | 132 |
| Flow, GPM | | 10 | 100 |
| Temperature rise, F | | 20 | 100 |
| Flue length, equiv. Ft. | | 6 | 80 |
| Air inlet length, equiv. Ft. | | 0 | 80 |
| Water volume, gals | 9.5 |
| Flue diameter, in | 5" |
| Current, amps | 5 |
| Cv, GPM @ 1psid | 60 |
| Boiler HP | 16 |
| Input MBH | 600 |
| Output MBH | 556 |
| Fuel Type | Nat. Gas |
| ASME Design Data Max | 100PSI +250°F |
| Negative Flue Pressure | -0.2" W.C. |
| Positive Flue Pressure | 0.25" W.C. |
| Height | 53 1/8" |
| Length | 36 3/4" |
| Width | 29 1/2" |
| LBS. | 859 lbs |
Improve your boiler efficiency while cutting your outside air louver size by 70 to 80% while maintaining an ideal boiler room environment
INTUITIVE and INTELLIGENT
The HeatNet integrated boiler control built into every KN can connect up to 16 units using only a
standard Ethernet cable: truly plug and play, with no external wall-mounted controls.
View>>
Rep Locator
Use our interactive map of North America to find the sales rep servicing your area.